Description
The ZCM Range features 6 models of cost-effective air-cooled liquid chillers, with cooling capacities ranging from 2.1kW to 6.7kW. These units are equipped with a coaxial heat exchanger, R410a refrigerant, and a 400v power supply for easy plug-and-play installation.
Suitable for both indoor and outdoor use, these chillers are ideal for industrial process cooling applications and come with a variety of features including a manual water fill system, an easy-view water level indicator, and a 2, 3, or 5 bar water pump. To provide reliability, continuity of operation, high performance, and reduced maintenance costs, these chillers are perfect for industrial applications across multiple sectors.
Standard Features
- R410 refrigerant gas
- Rotary compressor (108 – 116 models)
- Scroll (117 – 127 models)
- Crankcase heater
- Lowara / Ebara Pump
- Thermostatic valve
- High/low-pressure refrigerant gas gauges
- High/low-pressure switch
- Inspectable unit panels secured by screws
- Plastic water tank with level indicator
- Manual loading system
- Thermostat probe on water tank
- Plate heat exchanger
- Y-Strainer water filter (evaporator inlet)
- Dirty strainer alarm
- Evaporator inlet/outlet temperature probes
- Water by-pass with Inlet/outlet valve
- Water differential pressure switches (117+127 models)
- Flow switch (108+116 models)
- Condenser filter
- Fans without protection grid
- Microprocessor
- Phase sequence relay
- Thermomagnetic cut-out devices on every motor
- RS485 card set-up
- IP54 protection rate
- EASY MAINTENANCE
- PLUG & PLAY
Optional Features
- Pump with water gauge (P2, P3, P5)
- Compressor valves
- Electronic thermostatic valve
- RS485 connection cable
- Remote terminal
- Fan speed regulation
- Fan phase cut
- Set-point compensation with external sensor
- EC fans
- Condenser coil with cataphoresis protection
- Wheels kit
- Rubber anti-vibration kit
- Voltage 460/3/60HZ
Technical Data
PERFORMANCE
WATER 20/15 – AMBIENT 25°CZCM_STD
102
103
104
105
106
107
Cooling Capacity kW
2,1
3,1
4,3
5,1
5,9
6,7
Compressors absorbed power kW
0,3
0,6
0,8
0,9
1,1
1,3
EER 5,69
5,03
5,33
5,39
5,38
5,04
Water flow rate m3/h
0,35
0,54
0,74
0,87
1,02
1,14
PERFORMANCE WATER 12/7 – AMBIENT 35°C
ZCM_STD
102
103
104
105
106
107
Cooling Capacity kW
1,4
2,2
3,0
3,5
4,1
4,6
Compressors absorbed power kW
0,4
0,7
0,9
1,1
1,3
1,5
EER 3,46
2,83
3,08
2,85
2,87
2,82
Capacity m3/h
0,23
0,37
0,51
0,60
0,70
0,79
STAINLESS STEEL WATER TANK ZCM_STD
102
103
104
105
106
107
Capacità – Capacity Lt
25
25
25
25
25
25
AXIAL FANS ZCM_STD
102
103
104
105
106
107
Number / Ø Ø
1 / 250
1 / 300
1 / 300
1 / 350
1 / 350
1 / 350
Total nominal power kW
0,04
0,07
0,07
0,17
0,17
0,17
SOUND LEVEL PRESSURE ZCM_STD
102
103
104
105
106
107
Noise level dB(A)
47
47
47
47
47
47
NOMINAL PRESSURE PUMP ZCM_STD
102
103
104
105
106
107
P3 (1) kPa
335
315
276
251
251
229
Nominal power kW
0,37
0,37
0,37
0,37
0,37
0,37
P5 (1) kPa
573
549
506
478
475
451
Nominal power kW
0,55
0,55
0,55
0,55
0,55
0,55
Electrical Data
ELECTRICAL DATA ZCM_STD 102
103
104
105
106
107
FLI (kW) kW
1,05
1,36
1,64
1,94
2,24
2,47
FLA (A) A
5,65
7,14
8,54
9,94
11,04
12,34
ICF (A) A
24,65
27,14
34,54
35,94
46,04
45,34
Power supply V/Ph/Hz
220 / 1 / 50
REFRIGERANT GAS Type
R134a
R410a
PROTECTION RATE Type
IP33
IP44
DIMENSIONS & HYDRAULIC CONNECTIONS ZCM_STD
102
103
104
105
106
107
Length Mm
638
638
638
638
638
638
Width Mm
578
578
578
578
578
578
Height Mm
936
936
936
936
936
936
Weight Kg
63
95
97
100
105
105
Hydraulic connection size (ø) Inch
1/2
1/2
1/2
1/2
1/2
1/2